Xemex communication module
for Kamstrup Omnipower
Xemex communication module for Kamstrup Omnipower
The module is designed to fit into a Kamstrup Omnipower electricity meter.
Xemex’s product line includes a range of versatile Smart Meter data embedded communication modules, each designed with both grid operators and end users in mind. This communication module is no exception. The module is designed to fit into a Kamstrup Omnipower electricity meter.
A secure local maintenance interface on the E-meter provides direct access to the module (P0). The module is mains-powered.
The unit supports the industry-standard protocols M-Bus EN 13757-3&4 (P2) and DLMS-COSEM (P3). Data exchange with the acquisition system is realized via an IPv4 connection over GPRS, LTE Cat. M, 4G/3G or LTE Cat-1 technology. The data collection from peripheral energy meters relies on wireless M-Bus technology.
Status indicators on the front panel provide users with visual indication of the module’s operation. An optional extra relay contact enables calendar based switching of an external device
It is ideal for companies looking for a cost-effective, easy-to-use and easy-to-manage solution that simplifies firmware update, configuration and provisioning.
Xemex communication module for Kamstrup Omnipower
Downloads
Specs
General
- Real-time clock + calendar
- Clock sync during communication session
- Tamper detection
- Logging of events, errors and alarms
- Firmware remote upgradeable
- 4 wired M-Bus data channels
- Application is based on SMR5 specification
AMR
- Security: AES-128, DLMS/M-bus compliant
- Actual meter reads: Index registers in kWh
-
Periodic meter reads:
15-min intervals for 10 days
Storage for 40 daily reads
Storage for 13 monthly reads - Definable load profile: 960 entries w/ 20 configurable values each
- Calendar-based data logging
- Tariff control settings (day/night switching)
Interfaces – Data ports
- Supported bands: see specific datasheets
- PAP or CHAP authentification
- M-bus mini-master (P2): 4 channels
- Internal antenna and external antenna connector
- Local maintenance interface through optical port of the E-meter (P0)
Technical specifications
- Operating voltage Mains: 230V
- Power consumption Mains: 0.3W (idle) → 4.5W max
- Temperature range -40°C → 70°C
- Dimensions HxWxD (mm): 125 x 43 x 35
- Housing Compliant with Kamstrup Omnipower electricity meter
Variants
- 3G / 2G
- LTE-M / GPRS / NB IoT*
- 4G / 3G
* on roadmap